PX-49120 – Compact bulkhead emergency light IP65
PX-49120 IP65 Maintained

Compact bulkhead emergency light

The Polaryx PX-49120 is an IP65 waterproof, fire-retardant emergency luminaire equipped with 12 x 0.5W SMD 2835, delivering AC 200 Lm / DC 260 Lm. A rechargeable LiFePO4 3.2V 1800mAh cell provides 3-4 h of backup autonomy when mains power fails.

Luminous flux
200 Lm / 260 Lm
Autonomy
3-4 h
Battery
LiFePO4 3.2V 1800mAh
Power
Max 5.5W
Trade pricing on request Tell us the quantity and destination: you get a landed quote within one working day.
  • In stock · dispatched in 48 h
  • 3-year manufacturer warranty
  • Field-replaceable battery
  • Printed leaflet in every box

Specifications

Technical data

Values from the product datasheet. The same data is printed on the carton and in the leaflet.

Download the datasheet
Reference
PX-49120
LED type
12 x 0.5W SMD 2835
Luminous flux
AC 200 Lm / DC 260 Lm
Colour temperature
6000-7500K
Beam angle
120 deg
Colour rendering
CRI > 70
Power
Max 5.5W
Supply
AC 220-240V 50/60Hz
Battery
LiFePO4 3.2V 1800mAh
Autonomy
3-4 h
Charge time
15-18 h
Housing
FPA-10 PP flame-retardant
Colour
White / Translucent
Net weight
275 g
IP rating
IP65
Operating range
0C - 40C
Warranty
3 years
Operating mode
Maintained

Installation

Installation & wiring

Taken from the instruction leaflet supplied with every unit. Installation by qualified personnel.

Dimensions & mounting

Dimensions (L × H × D)
253.7 × 92.9 × 58.4 mm
Mounting
Wall or ceiling, surface
Terminals
L1 · L · N
Retail carton
258 × 96 × 51 mm
Battery protection
Overcharge & deep discharge

Status indicators

  • Green AC POWER on: mains present
  • Green off: battery fault

Wiring options

L1 · L · N

  • Maintained: L1 linked to L by the internal red jumper
  • Non-maintained: L1 left unconnected
  • Switch-controlled: L1 to external live via a wall switch

Installation steps

  1. 01

    Fix the base to the wall or ceiling with 5 × 30 PA screws.

  2. 02

    Connect the mains cable to the terminal block.

  3. 03

    Refit the reflector, then the transparent cover.

Precautions

Operating environment 0–40 °C.

On mains failure or low voltage the unit switches to emergency mode and returns to mains mode when supply is restored.

LiFePO4 battery: avoid drops and high temperatures; dispose of at an authorised battery collection point.

POLARYX · PX-49120
Instruction leaflet PX-49120 Open full size

Original instruction leaflet

Installation guide PX-49120

The printed sheet supplied with every unit, reproduced in full: everything needed on site to fix, wire and commission the luminaire.

Format
A5, double-sided
Language
English (original)
In the box
Printed copy with every unit
  • Precautions
  • Dimension drawing
  • Wiring diagram
  • Step-by-step mounting

Installation by qualified personnel in line with local wiring regulations. If in doubt, contact our technical desk.

Project supply

Send us your bill of quantities. You get landed cost within one working day.