Points of emphasis: where every emergency luminaire has to go

A lux calculation tells you how many luminaires an escape route needs. It does not tell you where some of them must be. EN 1838 and its companion code EN 50172 set out a list of positions that require a luminaire whatever the calculation says.

The fixed positions

A luminaire is expected near each exit door intended for emergency use, near stairs so that each flight receives direct light, near any other change of floor level, at each change of direction and at corridor intersections, and outside and near each final exit.

Safety equipment

Fire-fighting equipment, manual call points and first aid points must be lit so they can be found and used. The usual reference is 5 lux on the floor at the equipment.

Signs

Mandatory exit and safety signs along the route need to be illuminated in an emergency, either by an internally lit sign or by a luminaire placed so that the sign stays legible.

A practical sequence

Mark the points of emphasis on the plan first. Then fill the gaps along the route to meet the illuminance and uniformity figures. Working in that order avoids the common result of a route that passes the calculation but leaves a stair or an extinguisher in the dark.